Harris Series 5000/5500/6000 RTU OPC Server Configuration Guide

Channel Configuration

Protocol Mode Choose Protocol Mode
Master IOServer will initiate all requests.
Slave IOServer will wait for and response to requests.


Device Configuration

Station Address Address of slave. (0 to 63, 0 is the broadcast address)
Port Port 0 to Port 15
Type Type of Ports
Controls + Indicators 2-state controls and digital inputs
Analog Inputs 12 bits signed analogue input data
Accumulators 12, 24 or 32 bits unsigned input data
Set Points 12 bits unsigned analogue output
Raise / Lower Points Timed pulse output
Values Port configuration
Controls + Indicators controls:indicators controls is the number of controls and indicators is the number of digital inputs
Analog Inputs size size is number of analog inputs
Accumulators size:width size is the number of accumulators and width is the bit width of each accumulator (12, 24 or 32 bits)
Set Points size size is the number of set points
Raise / Lower Points size size is the number of Raise / lower points
Poll Type  
Ports Scan Port Online Status Scan (opcode 12)
Data Dump A/D and Accumulator Data Dump (opcode 0)
Status Dump Status Dump (opcode 5)
COS/SOE Status Check (opcode 3)
Interval (Sec) Interval between each poll. A value of zero will stop that type of poll.
Sync Time (Sec) Start of poll time within poll interval
Log COS Log received COS (Change of input Status) to the log file
Log SOE Log received SOE (Sequence of Events) to the log file

Variable Types

Note:

Sequence of Events SOE are reported by Ap.SOEi variables. The disabled status of SOE are reported by Ap.SDi variables.
Time Synchronization Writing a 1 to "Sync" will Synchronize the RTU clock to the current computer time using opcode 0x11 and 0x13. Writing a 0 to "Sync" will synchronize the RTU clock with opcode 0x11 and 0x13 with a time of zero.