| Modbus Protocol Type | Choose Modbus Protocol Type | ||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| RTU | Binary message format. 8 bits per data byte. | ||||||||||||||||||
| ASCII | ASCII message format. 16 bits per data byte. | ||||||||||||||||||
| Ethernet | Use Modbus/TCP message format. | ||||||||||||||||||
| Modbus Protocol Mode | Choose Modbus Protocol Mode | ||||||||||||||||||
| Master | IOServer wil initiate all requests. | ||||||||||||||||||
| Slave | IOServer will wait for and response to requests. | ||||||||||||||||||
| Buffer Size | Maximum of frame. 256 is the standard maximum frame size. | ||||||||||||||||||
| Initialization | The initial command sent to the device to check if the
device is online. In the form "BitAddress, Function Code, BitCount".
The default value is "0,3,16".
|

| Address | Device address of slave. |
|---|---|
| Register Address Size | Size of each register in the PLC. The default is two bytes per register location. |
| Non standard 1 origin addressing | Add 1 to address when requesting data. |
| Signed Integer | Treat all integers as signed. |
| 0 Origin addressing for bits in Registers. | Bits in registers are numbered 0 to 15. The default numbering is 1-16. |
| Reverse Bits in Registers | The bits in registers are reversed |
| 32 Bits Value Byte Ordering | Long value (4 bytes) byte ordering of device.
Device.40001,I4 will read the two registers at 40001 as a 32 bit signed integer value. |
| 32 Bits Floating Point Byte Ordering | Single Precision Floating point numbers byte ordering of device.
Device.40001,R4 will read the two registers at 4001 as a 32 bit floating point value. |
| 64 Bits Floating Point Byte Ordering | Double Precision Floating point numbers byte ordering of device. |

| .Master Value | |
| 255 | Master Mode, issue read and write function codes to slave |
| 0 | Issue write function code to slave, accept write function code from slave |
| n Seconds (1 to 254) | Issue read function code to slave for next n seconds, issue write function code to slave, accept write function from slave |
| .Master Value | |
| 255 | Slave Mode, accept read and write function codes from master |
| 0 | Accept read and write function codes from master |
| 1 | Accept read and write function codes from master, issue write function code to slave |
1, 2, 3, 4, 5, 6, 7, 15 and 16
IOServer running on a Pentium 4, 2.8 GHz PC under Windows 2000 Advanced Server reading from a remote device.
| Protocol | Requests per second |
|---|---|
| TCP/IP, 2 bytes per request | 2180 |
| TCP/IP, 250 bytes per request | 1392 |
| TCP/IP, 1450 bytes per request | 506 |
Last updated: 08 September 2010