| Ethernet |
Ethernet Link (Use AJ71E71 Ethernet
Interface Module). When configuring the TCP/IP port, the
port number and mode (TCP/IP or UDP/IP) must be the same
as that configured in the Melsec Ethernet module. Please
refer to Melsec Ethernet Interface Module User's manual
on how to configure it. Only Binary Code is supported. Use Unpassive
open format. Make
sure the dip switch on your Ethernet module is set as
follows
SW1: Line processing selection during TCP timeout
error. ON.
SW2: Data code setting. OFF for BINARY.
SW3-SW6: Not used, should be OFF.
SW7: CPU exchange timing setting. ON for write
enable
SW8: Initial timing setting. OFF.
|