Channel Configuration

| Serial |
Serial Link |
| Master |
IOServer will initiate all requests. |
| Slave |
IOServer will wait for and response to requests. |
| Set PLC to Monitor mode |
| On Write Error |
Set PLC to Monitor mode when a write to the
PLC caused an response code of 0x01 (Execution
was not possible because the PC is in RUN mode)
from the PLC. |
| At Start Up |
Set PLC to Monitor mode at startup |
| Never |
Never set the mode of the PLC |
|
| Buffer Size |
Maximum total buffer size. Use multi-frames block
format if more than 128 bytes is specified. |
Device Configuration

| Multi Link Station Address |
Address of Link Station. If disabled
then single link address mode is used. |
| Station Address |
Address of Device |
| PLC Type |
Support All C-Series and CV-Series PLC.
Use C-Series commands set. |
Variable Types

Notes:
Writing to bits in words is supported by reading the words,
modify the bits and writing it back to the PLC. Up to 464
contiguous bits can be written (for a 128 bytes buffer size) at a
time.
|